Table
A.4
Drive
Inputs
Analog
Speed
Reference
0
to
10
VDC
or
0
to
20
mA
Start
Edge-sensitive
signal
that
must
see
an
open-to-closed
contact
transition.
This
transition
may
be
a
momentary
or
fixed
closure.
Stop
An
open
contact
that
must
be
closed
when
the
drive
is
running.
The
drive
will
remain
off
as
long
as
the
contact
is
open.
IET
Reset
Edge-sensitive
signal
that
must
see
an
open-to-closed
contact
transition.
This
transition
may
be
a
momentary
or
fixed
closure.
Forward/Reverse
An
open
contact
to
assert
the
forward
direction
and
a
closed
contact
to
assert
the
reverse
direction.
Function
Loss
An
open
contact
that
must
be
closed
when
the
drive
is
running.
When
the
contact
is
open,
the
drive
turns
off.
The
drive
will
remain
off
as
long
as
the
contact
is
open.
Table
A.5
Drive
Outputs
Analog
Output
(0-10
VDC
scaled
signal)
The
scaled
signal
is
selected
through
parameter
F-29
and
can be
one
of
the
following:
*
Output
Voltage:
Oto
115
VAC
(M/N
1SU1xxxx
drives)
0
to
253
VAC
(M/N
1SU2xxxx
drives)
0
to
506
VAC
(M/N
1SU4xxxx
drives)
0
to
6382
VAC
(M/N
1SU5xxxx
drives)
*
%
Load
(Amps):
0
to
200%
(Percentage
of
output
amps
based
on
the
drive
nameplate.)
¢
RPM/Engineering
Unit:
Minimum
to
maximum
RPM
or
minimum
to
maximum
of
any
engineering
unit
(See
parameter
F-08)
*
%
Selected
Speed
Reference:
0
to
100%
(Percentage
of
the
selected
reference
signal
range.)
Snubber
Resistor
Braking
Snubber
resistor
control
signal
used
by an
optional
snubber
resistor.
Output
Status
Relay
115
VAC/24
VDC,
0.5
Amp,
relay
output
(One
Form
A
and
one
Form
B
contact
wired
with
a
single
common.)
A-2
SP500
AC
Drive
Installation
and
Operation
Manual