Parameter Descriptions
12-5
Displays the output frequency present at T1, T2, and T3 (U, V, and
W). This value includes reference, slip compensation, and IR
compensation.
Displays the value of the pre-ramp reference frequency command.
Displays the total output current present at T1, T2, and T3 (U, V, and
W), which includes torque and flux components.
Displays the amount of current that is in phase with the fundamental
voltage component. This is the torque-producing component of the
output current.
Displays the amount of current that is out of phase with the
fundamental voltage component. This is the magnetizing
component of the output current.
1 Output Freq
Range: +/-400.0 Hz [0.1 Hz]
Default: Read Only
Access: 0 Path: Monitor>Metering
See also:
2 Commanded Freq
Range: +/- 400.0 Hz [0.1 Hz]
Default: Read Only
Access: 0 Path: Monitor>Metering
See also:
3 Output Current
Range: 0.0 to Drive Rated Amps x 2 [0.1 Amps]
Default: Read Only
Access: 0 Path: Monitor>Metering
See also:
4 Torque Current
Range: Drive Rating x -2 to +2 [0.1 Amps]
Default: Read Only
Access: 1 Path: Monitor>Metering
See also:
5Flux Current
Range: Drive Rating x -2 to +2 [0.1 Amps]
Default: Read Only
Access: 1 Path: Monitor>Metering
See also: