Mounting the Drive
3-15
3.2.1 Verifying the Drive’s Watts Loss Rating
When mounting the drive inside another enclosure, determine the
watts loss rating of the drive from tables 2.4 through 2.6. These
tables list the typical full load power loss watts value @ 4 kHz carrier
frequency. Ensure that the enclosure is adequately ventilated and
the ambient air is within the specified temperature range:
NEMA 1: 0° to 50°C (32° to 122°F)
NEMA 4X: 0° to 40°C (32° to 104°F).