4-10
SP600 AC Drive User Manual
Table 4.5 – SP600 208/240 VAC Input Recommended Protection Devices
Model
Number
HP
Dual Element
Time Delay
Fuse
Non-time
Delay Fuse
Circuit
Breaker
1
ND HD Min
2
Max
3
Min
2
Max
3
Max
4
208 VAC Input
6SP201-2P2 0.5 0.33 6 6 6 10 15
6SP201-4P2 1 0.75 10 10 10 17.5 15
6SP201-6P8 2 1.5 15 15 15 30 30
6SP201-9P6 3 2 20 25 20 40 40
6SP201-015 5 3 20 35 20 70 70
6SP201-022 7.5 5 25 50 25 100 100
6SP201-028 10 7.5 35 70 35 125 125
240 VAC Input
6SP201-2P2 0.5 0.33 4 4.5 6 8 15
6SP201-4P2 1 0.75 6 9 10 15 15
6SP201-6P8 2 1.5 15 15 15 25 25
6SP201-9P6 3 2 20 20 20 35 35
6SP201-015 5 3 20 30 20 60 60
6SP201-022 7.5 5 25 45 25 80 80
6SP201-028 10 7.5 35 60 35 110 110
1
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum
2
Minimum protection device size is the lowest rated device that supplies maximum
protection without nuisance tripping.
3
Maximum protection device size is the highest rated device that supplies drive protection.
For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
4
Maximum allowable by US NEC. Exact size must be chosen for each installation.