2-4
SP600 AC Drive User Manual
.
Table 2.3 – 208/240 VAC Power Ratings
NEMA 1, NEMA 4,
Flange
Model Number
1
1
For NEMA 1 drives, replace “yz” in the model number with 01. For NEMA 4X drives, replace “yz” with 4X.
Nominal Power
Ratings
Input
KVA
Input
Amps
Output Amps@ 4 kHz
2
2
For higher carrier frequencies, refer to chapter 12, parameter 151.
Watts
Loss @
4 kHz
110%
OL Duty
150%
OL Duty 208 VAC Input 240 VAC Input
HP kW HP kW
208
VAC
240
VAC
208
VAC
240
VAC Cont.
1
min
3
sec Cont. 1 min 3 sec
6SP2yz-2P2xxxx 0.5 0.37 0.33 0.25 1.1 1.2 2.9 2.5 2.5 2.7 3.7 2.2 2.4 3.3 45
6SP2yz-4P2xxxx 1.0 0.75 0.75 0.55 2.0 2.3 5.6 4.8 4.8 5.5 7.4 4.2 4.8 6.4 68
6SP2yz-6P8xxxx 2.0 1.5 1.5 1.1 3.6 4.2 10.0 8.7 7.8 10.3 13.8 6.8 9.0 12.0 88
6SP2yz-9P6xxxx 3.0 2.2 2.0 1.5 5.1 5.8 14.0 12.2 11.0 12.1 16.5 9.6 10.6 14.4 130
6SP2yz-015xxxx 5.0 4.0 3.0 3.0 5.8 6.7 16.0 13.9 17.5 19.2 26.2 15.3 17.4 23.2 240
6SP2yz-022xxx 7.5 5.5 5.0 4.0 8.4 9.7 23.3 20.2 25.3 27.8 37.9 22.0 24.2 33.0 307
6SP2yz-028xxxx 10 7.5 7.5 5.5 10.7 12.4 29.8 25.8 32.2 37.9 50.6 28.0 33.0 44.0 420