Parameter Descriptions
12-51
If the drive faults repeatedly for more than the number of attempts
specified in Auto Rstrt Tries with less than five minutes between
each fault, the drive will remain in the faulted state. The fault Auto
Rstrt Tries will be logged in the fault queue.
The auto restart feature is disabled when the drive is stopping and
during autotuning. Note that a DC Hold state is considered
stopping.
The following conditions will abort the reset/run process:
Issuing a stop command from any control source. (Note that
removal of a 2-wire run-fwd or run-rev command is considered a
stop command.)
Issuing a fault reset command from any active source.
Removing the enable input signal.
Setting Auto Restrt Tries to zero.
Occurrence of a fault that is not auto-resettable.
Removing power from the drive.
Exhausting an auto-reset/run cycle.
Note that two autotuning status bits are provided in Drive Status 2
(210): an active status bit and a countdown status bit.
Sets the time between restart attempts when the auto restart
feature is enabled. Refer to Auto Rstrt Tries (174) for more
information about the auto restart feature.
175 Auto Rstrt Delay
Range: 0.5 to 30.0 Sec [0.1 Sec]
Default: 1.0 Sec
Access: 1 Path: Dynamic Control>Stop/Restart Modes
See also: 174