Parameter Descriptions
12-55
Enables/disables the feature that saves the present MOP
(motor-operated potentiometer) frequency reference at power down
and/or at stop. If the drive is re-started or powered up, the setpoint
will be restored with the last active MOP output value.
Important: The MOP feature requires that the digital inputs be
configured for MOP Inc and MOP Dec (see 361-366).
Sets the rate of change of the MOP reference in response to a
digital input.
194 Save MOP Ref
Range: See figure 12.26
Default: See figure 12.26
Access: 2 Path: Utility>MOP Config
See also:
Figure 12.26 – Save MOP Ref (194)
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1=Save
0=Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
At Stop
Nibble 1Nibble 2Nibble 3Nibble 4
Figure 12.27 – Configuring Digital Inputs for MOP Inc and MOP Dec
Dig In #
Dig In #
Dig In #
Dig In #
+24 V
MOP Inc
MOP Dec
195 MOP Rate
Range: 0.2 to Maximum Freq [0.1 Hz/sec]
Default: 1.0 Hz/sec
Access: 2 Path: Utility>MOP Config