Parameter Descriptions
12-59
Configures behavior of User Sets. Dynamic switching between sets
is permitted from either digital input states of parameter value.
Bit 0 - Dynamic Mode - Specifies User Sets operating mode.
0 = Disabled: Disabled causes normal operation.
1 = Enabled: Enabled selects Dynamic Mode. While enabled,
parameters changes are not saved in active non-volatile storage.
Bit 1 - Ctrl Source - Defines which source controls the selection of
user sets, while Dynamic Mode is enabled.
0 = Dig. Inputs: Dig. Inputs refers to UserSetBitn defined by
Terminal Block Input(s) from Digital ln 1-6 Sel (361-366).
1 = DynUsrSetSel: DynUsrSetSel (205) determines the active User
Set.
Controls which User Set is in memory when Ctrl Source (bit 1) of
DynUsrSetCnfg (204) is set to DynUsrSetSel.
204 Dyn UserSet Cnfg
Range: See figure12.28
Default: See figure 12.28
Access: 2 Path: Utility>Drive Memory
See also: 205, 206, 361-366
Figure 12.28 – Dyn UserSet Cnfg
205 DynUsrSetSel
Range: See figure12.29
Default: See figure 12.29
Access: 2 Path: Utility>Drive Memory
See also: 204, 206
0xx 0xxxxxxxxxxxx
10 01234567891112131415
Bit 0:
1=Enabled
0=Disabled
Bit 1:
1 = DynUsrSetSel
0 = Digital Inputs
x = Reserved
Bit #
Factory Default Bit Values
Dynamic Mode
Ctrl Source
Nibble 1Nibble 2Nibble 3Nibble 4