Parameter Descriptions
12-67
Displays the accumulated percentage of motor overload.
Continuously operating the motor over 100% of the motor overload
setting will increase the value of Motor OL Count to 100% and
cause a drive fault.
Captures and displays the output frequency of the drive at the time
of the last fault.
Captures and displays motor amps at the time of the last fault.
Captures and displays the DC bus voltage of the drive at the time of
the last fault.
220 Motor OL Count
Range: 0.0 to 100.0 % [1.0%]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 47, 48
224 Fault Frequency
Range: 0.0 to +/-400.0 Hz [0.1 Hz]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 225-230
225 Fault Amps
Range: 0.0 to Rated Amps x 2 [0.1 Amps]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 224-230
226 Fault Bus Volts
Range: 0.0 to Max Bus Volts [0.1 VDC]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 224-230