EasyManua.ls Logo

Rockwell Automation Reliance electric SP600 Series - Page 228

Rockwell Automation Reliance electric SP600 Series
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12-98
SP600 AC Drive User Manual
Selects the drive status that will energize an output relay.
1 = Fault: A fault has occurred and stopped the drive.
2 = Alarm: A Type 1 or Type 2 alarm condition exists.
3 = Ready: The drive is powered, Enabled, and no start inhibits
exist. It is “ready” to run.
4 = Run: The drive is outputting voltage and frequency to the motor
(indicates 3–wire control, either direction).
5 = Forward Run: The drive is outputting voltage and frequency to
the motor (indicates 2–wire control in forward).
384 Digital Out2 Sel
Range:
1 = Fault
1
2 = Alarm
1
3 = Ready
4 = Run
5 = Forward Run
6 = Reverse Run
7 = Auto Restart
8 = Reserved
9 = At Speed
10 = At Freq
2
11 = At Current
2
12 = At Torque
2
13 = At Temp
2
14 = At Bus Volts
2
15 = At PI Error
2
16 = DC Braking
17 = Curr Limit
18 = Economize
19 = Motor Overld
20 = Power Loss
21 = Input 1 Link
22 = Input 2 Link
23 = Input 3 Link
24 = Input 4 Link
25 = Input 5 Link
26 = Input 6 Link
27 = TB in Manual
Default: 4 = Run
Access: 1 Path: Inputs & Output>Digital Outputs
See also: 1 - 4, 12, 48, 53, 137, 147, 157, 184, 218, 381-383,
385, 386
1
Any relay programmed as fault or alarm will energize (pick up) when power
is applied to the drive and de-energize (drop out) when a fault or alarm
exists. Relays selected for other functions will energize only when that
condition exists and will de-energize when the condition is removed.
2
Activation level is defined in Dig Out “x” Level (381, 385).

Table of Contents

Related product manuals