SP600 AC Drive User Manual
24 = Input 4 Link: Outputs the state of digital input 4.
25 = Input 5 Link: Outputs the state of digital input 5.
26 = Input 6 Link: Outputs the state of digital input 6.
27 = TB in Manual: Terminal block has manual reference control.
Sets the relay activation level for options 10-15 in parameter 384
(Digital Out2 Sel). Units are assumed to match the selection in
parameter 384 (i.e., At Freq = Hz, At Torque = Amps).
Sets the on delay time for the digital outputs. This is the time
between the occurrence of a condition and activation of the relay.
385 Dig Out2 Level
Range: 0.0 to 819.2 [0.1]
Default: 0.0
Access: 1 Path: Inputs & Output>Digital Outputs
See also: 384
386 Dig Out2 OnTime
Range: 0.00 to 600.00 Sec [0.01 Sec]
Default: 0.00 Sec
Access: 2 Path: Inputs & Output>Digital Outputs
See also: 384