EasyManua.ls Logo

Rockwell Automation Reliance electric SP600 Series - Table A.8 - Derating Guidelines:- SP600 Ambient Termperature;Load

Rockwell Automation Reliance electric SP600 Series
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
A-9
Table A.8 – Derating Guidelines:- SP600 Ambient Termperature/Load
Frame Class Enclosure Freq Derate
A 400V Open,
NEMA Type
1, IP20,
Flange
2-10 kHz None
B 400V Open,
NEMA Type
1, IP20,
Flange
2-10 kHz None
C 400V NEMA Type
1, Flange
2-8 kHz None
10 kHz
D 400V NEMA Type
1, Flange
NEMA Type
4X/12
*
2-6 kHz None
8-10 kHz
E NEMA Type
1, Flange
NEMA Type
4X/12
2-4 kHz None
6-12 kHz
*
NEMA Type 4X/12 D frame drives have a maximum ambient of 40 degrees C.
NEMA Type 4X/12 D frame drives have a maximum ambient of 40 degrees C.
10
20
30
40
50
60
40 50 60 70 80 90 100
% Full Load Amps
Ambient Temp
8 K
12 K
2 K
4 K