SECTION [32] BURGLARY / FIRE BELL CUT-OFF TIMINGS
These timings (burglary bell cut-off timing and fire bell cut-off timing) establish siren
activation timings in case of any “fire alarmsand audible “burglary alarmsrespectively will
occur in the system.
While the panel is within the “main programming menu”, to program the Burglary / Fire
Bell cut-off timings, select section [32] and enter 2 groups of 2 digits each (01 to 99
minutes).
The following sequence will be introduced:
|__|__||__|__| |0 3||1 0| by default
After the first 2 digits, the keypad buzzer will sound 3 beeps and after the last 2 digits it will
sound 6 beeps, exiting this section and waiting for a new command to enter another section
or to exit the programming menu.
If one of the 2 timings should keep their previously programmed values press [#] key instead
of the 2 corresponding digits.
Notes:
1. A fire alarm may be triggered by a “firezone type or from the keypad, by pressing [7]+[9]. Any fire alarm
will be only as “audibleand “pulsingtype and it will trigger the “fire bell cut-off timing”, too;
2. Other kind of alarms may be triggered by other zone types (differed of fire) or from the keypad, by [*]+[#]
or [1]+[3]) pressing. If zones are audible and the special alarms from keypad activates the siren too, they
will trigger the “burglary bell cut-off timing”;
3. Once any audible zonetriggered the siren that zone will not retrigger anymore the „siren activation timing”
and it will not record anymore alarms in the 425-event LOG, each time it will get violated. If another audible
zone is violated while the siren was started before, the siren activation timing will be retriggered again.
Means if a zone triggered the siren activation timingonce and then, during same siren activation period, its
loopclosesand opensfor several times, that zone will not trigger again the siren activation timingand it
will not record again alarms in the 425-event LOG.
SECTION [33] „TIME WINDOW FOR INTELLIZONES
Enter 3 digits (001 to 255 seconds) in order to set the „time window for intellizones”.
The following sequence will be introduced:
|__|__|__| |050| by default (50 sec.)
The keypad buzzer will sound 6 confirmation beeps after the 3-digit group and the panel exits
the section, waiting for a new command to enter another section.
To exit the „main programming menu”, press [#] key.
Note: For the “time window for intellizones” any value from 000 to 999 may be entered, but the panel will
automatic adjust the introduced value by modulo 256 and will record the result in memory as programmed
value. If the result of adjustment is 0, there will be no “time window for intellizones” and all zones in the system
will respond as normal, even for some of them their intellizone attribute were set as enabled!
SECTION [34] - DELAY FOR „AC POWER LOSS / RESTORE TRANSMISSION (01-99 MINUTES)
The „AC power loss / restoretransmission delay (0199 minutes) sets the time lapse before
which the „AC power loss / restore events will be reported to the “central station(or before
the sound dialer starts synthesis sounds transmission). If in the meantime the AC power is
restored, the event code (or the synthesis sound) will not be transmitted anymore.
While the panel is within the “main programming menu”, to program the delay for AC
power loss / restore transmission, select section [34], and enter the 2-digits
number corresponding to the number of minutes (01 to 99 minutes).
The following sequence will be introduced:
|__|__| |02| by default
After the 2 digits have been entered, the keypad buzzer will sound 6 beeps and exit section
[34], waiting for a new command to enter another section or to exit the programming menu.
If the respective time should keep their previously programmed values press [#] key instead
of the 2 digits.
SECTION [35] - ACTIVATION TIME FOR PGM1 AND PGM2, DEFINED AS PULSE TYPE (001 TO 255 SECONDS)
Activation times (001 to 255 seconds) for PGM1 and PGM2 defined as pulse types stand for
the number of the seconds during which each pulse PGM type will be activated to GND.
While the system is within „main programming menu”, to set the „activation times” for
PGM outputs defined as pulse types, select section [35] and then enter 2 groups of
3 digits (001 to 255 seconds).
The following sequence will be introduced:
|__|__|__||__|___|__| |003||003| by default