EasyManua.ls Logo

Rosemount 3095FB - Entered Scale Factor and Offset

Rosemount 3095FB
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Manual
00809-0100-4738, Rev DA
May 2006
4-12
Rosemount 3095FB
Figure 4-10. Integer Scaling - Entered Endpoints Screen
Entered Scale Factor and Offset
Entered Scale Factor and Offset converts floating point numbers into
integers through the equation:
where
y = scaled integer output
x = measured value of PV in current units
A = scale factor
B = offset of scaled integer
For more information, see section 5.3.1.2 in the Modbus Protocol Guide
located in chapter 3 of the manual.
1. Define the maximum integer count.
2. Calculate the scale factor (“A” in above equation) for each process
variable.
3. Calculate the offset (“B” in above equation) for each process variable.
4. Click Set Scaling to implement changes.
yA()x() B 32768()=

Table of Contents

Related product manuals