Reference Manual
00809-0100-4021, Rev FB
August 2011
4-9
Rosemount 3144P
FOUNDATION Fieldbus
Table 4-2.
RB.RECOMMENDED_ACTION
Resource Block
Diagnostics
Table 4-3. Resource Block
BLOCK_ERR messages
Block Errors
Table 4-3 lists conditions reported in the BLOCK_ERR parameter.
Table 4-4. Resource Block
SUMMARY_STATUS messages
Alarm Type
Failed/Maint/Advise
Active Event
Recommended Action
Text String
PlantWeb Alerts
None None No action required
Advisory
NV Writes Deferred Non-volatile writes have been deferred, leave
the device powered until the advisory goes
away
Maintenance
Configuration Error Re-write the Sensor Configuration
Primary Value
Degraded
Confirm the operating range of the applied
sensor and/or verify the sensor connection and
device environment
Calibration Error Retrim the device
Secondary Value
Degraded
Verify the ambient temperature is within
operating limits
Failed
Electronics Failure Replace the Device
HW / SW Incompatible Verify the Hardware Revision is compatible
with the Software Revision
NV Memory Failure Reset the device then download the Device
Configuration.
Primary Value Failure Verify the instrument process is within the
Sensor range and / or confirm sensor
configuration and wiring.
Secondary Value
Failure
Verify sensor range and/or confirm sensor
configuration and wiring
Diagnostic
Error
Sensor Drift Alert or Hot
BU active
Confirm the operating range of the supplied
sensor and/or verify the sensor connection and
device environment
Primary Value
Degraded
Confirm the operating range of the supplied
sensor and/or verify the sensor connection and
device environment
Condition Name and Description
Other
Device Needs Maintenance Now
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost.
Device Needs Maintenance Now
Out of Service: The actual mode is out of service.
Condition Name
No repair needed
Repairable
Call Service Center