EasyManua.ls Logo

Rosemount 3144P - FOUNDATION Fieldbus

Rosemount 3144P
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Manual
00809-0100-4021, Rev FB
August 2011
Rosemount 3144P
2-12
NOTE
Do not connect the power/signal wiring to the test terminal. The voltage
present on the power/signal leads may burn out the reverse-polarity
protection diode built into the test terminal. If the test terminal’s reverse
polarity protection diode is burned out by the incorrect power/signal wiring, the
transmitter can still be operated by jumping the current from the test terminal
to the “–” terminal. See “Test Terminal (HART / 4–20 mA only)” on page 5-2
for use of the terminal.
Figure 2-10. Connecting a Field
Communicator to a
Transmitter Loop (HART/ 4–20
mA).
FOUNDATION fieldbus
Figure 2-11. Transmitter
Terminal Block
Power/Signal Terminals
The signal wire may be grounded at
any point or left ungrounded.
Power
Supply
250 R
L
1100
AMS software or a Field Communicator can be connected at any termination
point in the signal loop. The signal loop must have between 250 and 1100 ohms
load for communications.
or*
Sensor
Terminals
(1 – 5)
Ground
Power
Terminals
Power
Terminals
Ground
Sensor
Terminals
(1 – 5)
WIRING CONNECTIONS
WIRING CONNECTIONS
(with “T1” integral transient protection option)
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for Rosemount 3144P

Related product manuals