Reference Manual
00809-0100-4021, Rev FB
August 2011
4-31
Rosemount 3144P
FOUNDATION Fieldbus
Figure 4-5. Problems with
communications flowchart
COMMUNICATIONS ESTABLISHED BUT HAVE
“BLOCK_ERR” OR AN “ALARM” CONDITION.
See “PlantWeb™ Alerts” on page 4-6
Read the following parameters in the
Resource Block to determine the
recommended action.
BLOCK_ERR (see Table 4-3)
SUMMARY_STATUS (see Table 4-4)
DETAILED_STATUS (see Table 4-5)
Problem Identified?
Yes
No
Perform Recommended
Action, see Table 4-5.
For more detailed
information
Perform the following steps in the Sensor
Transducer Block to determine the
recommended action.
BLOCK_ERR (see Table 4-6)
XD_ERR (see Table 4-7)
DETAILED_STATUS (see Table 4-8)
RECOMMENDED_ACTION (see Table 4-8)
SENSOR_DETAILED STATUS (see Table 4-8)
If error condition does not exist
in the Resource Block then it is a
configuration problem, see “AI
BLOCK_ERR Conditions.” in
Table 4-10
Problem Identified?
Yes
No
If the problem persists
contact your local
Emerson representative.
Problem Identified?
Perform Recommended
Action, see Table 4-8.
Yes
No
Perform Recommended
Action, see Table 4-11.
Yes
No
Perform Recommended
Action, see Table 4-13 on
page 4-32.
Problem Identified?