5.2.11 Return to Factory Default Settings
You must be very careful before using this command! This
erases the entire memory and returns all codes to their
factory default setting.
To return to factory default settings:
1. Enter Programming mode.
2. Press 0 to enter Menu 0.
The Transmit LED flashes red.
The Program LED flashes red.
3. Enter your Programming code.
If the Programming code is valid, all memory is erased, you hear
three beeps and the controller returns to Normal mode.
If the Programming code is invalid, you hear a long beep and the
controller returns to Normal mode without erasing the memory of
the controller.
5.2.12 Replacing a Lost Programming Code
In the event that the Programming code is forgotten, the AYC-
E/Q/T60 may be reprogrammed in the field using the following
instructions:
To replace a lost Programming code:
1. Remove power from the reader.
2. Activate the tamper by removing the reader from the wall or
removing the reader's case.
3. Apply power to the reader.
4. You now have 10 seconds to enter Programming mode using the
factory default Programming code 1234.
Mode/Transmit
Door/Program
Green
Mode/Transmit
Door/Program
Red
Red

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rosslare AYC-Q60 and is the answer not in the manual?

Rosslare AYC-Q60 Specifications

General IconGeneral
BrandRosslare
ModelAYC-Q60
CategoryCard Reader
LanguageEnglish

Related product manuals