EasyManuals Logo

Satec EM133 User Manual

Satec EM133
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Chapter 5 Configuring the EM13X Series Configuring Communications
76 EM13x Series SMART MULTIFUNCTION METER
Setting up the Ethernet
Using the Front Display
Select Net from the main menu. See Viewing and Changing Setup
Options in Chapter 3 for information on navigating in menus.
See the table below for available network options.
Using PAS
Select Communications Setup from the Meter Setup menu, and then
click on the Network Setup tab.
Figure 5-2: Communication Setup Dialog Box Network Setup Tab
The following table lists available network options.
Table 5: Ethernet Setup Options
Display Label
Parameter
Default
IP Address
Device IP Address
192.168.0.203
Subnet Mask
Network Subnet Mask
255.255.255.0
Def. Gateway
Network Default Gateway
192.168.0.1
TCPServicePort
502 = Modbus/TCP
20000 = DNP3/TCP
502
NOTES
The meter provides the permanent MODBUS TCP server on port 502.
Selecting the DNP3 TCP service port launches the second DNP3 TCP
server allowing simultaneous connections on both TCP ports. Selecting
the Modbus TCP port disables the DNP3 TCP server.
The TCP service port can also be changed trough the COM2 serial
port setup. Changing the communication protocol for the port
automatically changes the TCP port for the Ethernet.
When you change the device network settings through the Ethernet port,
the device port restarts so communication will be temporarily lost. You
Net IP Address
192.168.000.203

Table of Contents

Other manuals for Satec EM133

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec EM133 and is the answer not in the manual?

Satec EM133 Specifications

General IconGeneral
BrandSatec
ModelEM133
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals