automatically update the “Parameter” box with the
following parameter in the group.
8. Add the name for your data log file in the “Name” box. It
will appear in the data log reports.
9. Save your new setup to the device database, and send it
to the meter.
Factory Preset Periodic Data Logs
Data logs #1 and #2 are factory preset for periodic recording of
the standard power quantities as shown in the following table.
TOU Profile Data Log Files
Data log #16 is configurable to store TOU daily profile log
records on a daily basis.
A TOU profile log file is organized as a multi-section file that
has a separate section for each TOU energy and maximum
demand register. The number of sections is taken automatically
from the Summary/TOU Registers setup (see Setting up Total and
Tariff Registers). If you selected to profile TOU maximum
demands along with energy registers, then the number of
sections in the file will be twice the number of the allocated
TOU registers.
To configure a TOU daily profile log file:
1. Configure your TOU registers and TOU schedule in the
meter before allocating memory for the profile log file (see
Setting up Total and Tariff Registers).
2. Double click on the Data Log#16 partition with the left
mouse button.