The low and high values of these set points may be assigned either to (regardless of the operating mode):
gross measurement
net measurement
- Motion: The outputs can be assigned to copying measurements stability.
- Defective measurement: The output level is set when the internal alarm flag described in “Weighing diagnosis” § in
the MEASUREMENT AND STATUS § is activated. This allows to warn about defection of the measurement chain.
Dosing alarms are not considered as defective measurements.
- Input image: Outputs can be assigned to copying inputs state, either using the same logic or inverting the input state
(negative logic). Outputs 1 and 3 are assigned to input 1 and outputs 2 and 4 are assigned to input 2.
- level on request: the input level is driven by master requests.
10.3 Functions attached to an operating mode:
See corresponding sections for a complete description.
10.4 Feeding mode in dosing processes
For the filling and dosing by unloading operating modes, it is possible to select the activation order of the feed
outputs:
coarse feed then fine feed after coarse feed stop
coarse feed + fine feed at the beginning of the cycle
coarse feed only
fine feed then coarse feed then fine feed
Fine feed then fine feed and coarse feed simultaneously then fine feed
High feed then coarse feed then fine feed
high feed and coarse feed and fine feed simultaneously
high feed and coarse feed simultaneously then fine feed
10.5 Analog output (IO+ version)
An optional analog board in current and voltage might be used with eNod4 to provide IO+ version. This must be asked
when ordering eNod4 product.
Voltage output might be set either 0-5V or 0-10V, and the current output to 4-20mA, 0-24mA, 0-20mA or 4-20mA with
alarm at 3.6mA. Both output (current and voltage) might separately be enable. Settings are effective after eNod4
reset.