78
SCAIME Manual : NU-eNod4D-ETH-E-0418_216710-E.docx
Page 1/2
Automatic correction [Yes], [No]
If enable, In-flight level is automatically corrected at each end
of cycle.
In-Flight weight Level ±500 000
In-flight Level corresponds to the weight of product that
carries on falling after the FF output is disabled. Its value can
be automatically corrected.
Min / Max In-Flight
level
±32768
Min In-flight Level < In-flight Level < max In-flight Level. If this
condition is not satisfied, In-flight is not changed.
If these levels are zero, there is no control of limits. But
regardless of these limitations, the value calculated
automatically is limited to FF level.
Page 2/2
Correction % 0 – 100 %
If Automatic correction enabled, the correction formula is:
In-flight = In-flight + (Dosing result – Target weight) x
Correction %.
X3 correction if Out of
Tolerance
[Yes], [No]
If the Dosing result is out of Tolerance, ‘Correction %’ is
multiplied by 3 (limited at 100 %) inside the correction
formula.
13.2.5 Flow rate control settings
Parameter Possible Value Description
Flow rate control parameters
Min. weight
variation
0 – 65535
Enable if time interval >0. If during ‘Time interval’, the net
measurement has been changed of less than the ‘minimal weight
variation’, then the cycle is stopped and a flow rate error is
detected.
Time Interval 0 – 65535 ms