22 Vers. 1.0 2024_03
Power consumption calculator
When planning, it is worth considering a reserve of at least 10% due to possible future
expansions. Exit luminaires and safety luminaires can be placed on the circuits as required.
It is possible to use nodes and branches - this does not affect the quality of communication.
The following table shows the maximum permissible cable length for an electrical circuit with
a circuit load of 1A, 2A, 3A for 1.5mm² or 2.5mm² cables.
Current
consumption (A)
Cross section
3A
1.5mm²
2A
1.5mm²
1A
1.5mm²
3A
2.5mm²
2A
2.5mm²
1A
2.5mm²
Average current consumption:
Exit sign 1W: 80mA
Safety luminaire 3W: 170mA
Safety luminaire 4W: 220mA
Safety luminaire 6W: 300mA
SECURO 24 PRO panel: 650mA