Installation and operating instructions
8 Vers. 1.0 2024_03
1.4 Technical Data
Addressable 24V DC low power supply system (LPS)
1-hour (NCCB2461E.): 534x475x186mm
3-hour (NCCB2463E.): 754x475x186mm
Housing color and material:
White plastic, gray metal
Degree of protection / protection
class:
Max. current consumption LPS:
Supply voltage
output circuits:
6 circuits with max. 3 A load each and max. 20 addressable
luminaires per circuit
18A in emergency operation, 10A continuous load capacity
Recommended connection
cross-sections:
Mains cable: 1.5 - 10mm² rigid
Final circuits: 1.5 - 2.5mm² rigid
Automatic, based on the factory-set unique identification
number
1-hour 2 x 45Ah OGiV (NCCB2461E.)
3-hour 4 x 45Ah OGiV (NCCB2463E.)
NCCB2461E.without batteries: 14kg, incl. batteries: 43kg
NCCB2463E.without batteries: 17kg, incl. batteries: 75kg
Commissioning SW Schrack SECURO, graphics module
Schrack SECURO Graphics, client software Schrack SECURO
Client
5" touchscreen panel, system information with the last 2000
event data
4 freely configurable relays for fault messages
Max. 254 control panels with TCP/IP network communication,
max. 32 control panels with network for RS485 ring topology
Max. 32 addressable voltage monitoring modules for monitoring
general lighting distribution boards
10° to 35°C
for maximum battery life: constant 25°C