Date Code 20010518 “Job Done” Examples - (Example 3) 4-33
SEL-2020 Instruction Manual
5. Use the SET A 11 command to define a trigger condition (CMD1 is asserted) and a message
the SEL-2020 sends to the RTU on Port 11. The message (MESG1) is a string you build that
extracts current and voltage meter data from Ports 1 through 7.
Your screen should look similar to the following:
*>>SET A 11<ENTER>
SET A 11<ENTER>SET A 11<ENTER>
SET A 11<ENTER>
Automatic message settings for Port 11
Auto-message Settings
How many auto-message sequences (0-12) MSG_CNT = 0 ? 1<ENTER>
1<ENTER>1<ENTER>
1<ENTER>
Item 1 trigger D1
ISSUE1 = NA
? CMD1<ENTER>
CMD1<ENTER>CMD1<ENTER>
CMD1<ENTER>
Item 1 message
MESG1 = ""
? \
\\
\Rf;1:METER:IA/,
Rf;1:METER:IA/,Rf;1:METER:IA/,
Rf;1:METER:IA/,\
\\
\Rf;1:METER:VA/,
Rf;1:METER:VA/,Rf;1:METER:VA/,
Rf;1:METER:VA/,\
\\
\Rf;2:METER:IA/,
Rf;2:METER:IA/,Rf;2:METER:IA/,
Rf;2:METER:IA/,\
\\
\Rf;2:MET
Rf;2:METRf;2:MET
Rf;2:METER:VA/,
ER:VA/,ER:VA/,
ER:VA/,\
\\
\<ENTER>
<ENTER><ENTER>
<ENTER>
? \
\\
\Rf;3:METER:IA/,
Rf;3:METER:IA/,Rf;3:METER:IA/,
Rf;3:METER:IA/,\
\\
\Rf;3:METER:VA/,
Rf;3:METER:VA/,Rf;3:METER:VA/,
Rf;3:METER:VA/,\
\\
\Rf;4:METER:IA/,
Rf;4:METER:IA/,Rf;4:METER:IA/,
Rf;4:METER:IA/,\
\\
\Rf;4:METER:VA/,
Rf;4:METER:VA/,Rf;4:METER:VA/,
Rf;4:METER:VA/,\
\\
\<ENTER>
<ENTER><ENTER>
<ENTER>
? \
\\
\Rf;5:METER:IA/,
Rf;5:METER:IA/,Rf;5:METER:IA/,
Rf;5:METER:IA/,\
\\
\Rf;5:METER:VA/,
Rf;5:METER:VA/,Rf;5:METER:VA/,
Rf;5:METER:VA/,\
\\
\Rf;6:METER:IA/,
Rf;6:METER:IA/,Rf;6:METER:IA/,
Rf;6:METER:IA/,\
\\
\Rf;6:METER:VA/,
Rf;6:METER:VA/,Rf;6:METER:VA/,
Rf;6:METER:VA/,\
\\
\<ENTER>
<ENTER><ENTER>
<ENTER>
? \
\\
\Rf;7:METER:IA/,
Rf;7:METER:IA/,Rf;7:METER:IA/,
Rf;7:METER:IA/,\
\\
\Rf;7:METER:VA/
Rf;7:METER:VA/Rf;7:METER:VA/
Rf;7:METER:VA/\
\\
\n<ENTER>
n<ENTER>n<ENTER>
n<ENTER>
Archive Settings
Enable use of archive data items (Y/N) ARCH_EN = N ? <ENTER>
<ENTER><ENTER>
<ENTER>
Size of user-defined data space in registers USER = 0 ? <ENTER>
<ENTER><ENTER>
<ENTER>
MSG_CNT = 1
ISSUE1 = 11:CMD1
MESG1 ="\RF;01:METER:IA/,\RF;01:METER:VA/,\RF;02:METER:IA/,\RF;02:METER:VA/
,\RF;03:METER:IA/,\RF;03:METER:VA/,\RF;04:METER:IA/,\RF;04:METER:VA/
,\RF;05:METER:IA/,\RF;05:METER:VA/,\RF;06:METER:IA/,\RF;06:METER:VA/,
\RF;07:METER:IA/,\RF;07:METER:VA/\n"
ARCH_EN = N
USER = 0
Save changes (Y/N) ? Y<ENTER>
Y<ENTER>Y<ENTER>
Y<ENTER>
Port 11 Settings Changed
*>>
Notes: Enter 1 because you want to define one message trigger and one message.
Set ISSUE1=CMD1 to trigger MESG1 when the SEL-2020 CMD1 element asserts.
! Set MESG1 as shown in the above screen to retrieve the A-phase current and voltage
data stored in the database on each of the SEL relay ports, 1 through 7. Data are defined
with a string format of \Rf;(Port number):(Data region label):(Data item label)/, where
\Rf:...../ requests the data in floating-point format.