4-48 “Job Done” Examples - (Example 5) Date Code 20010518
SEL-2020 Instruction Manual
To print long event reports from all seven Port A3 archive data regions, you set Port 9 ISSUE 2=:
!1:ARCH3*!2:ARCH3*!3:ARCH3*!4:ARCH3*!5:ARCH3*!6:ARCH3*!7:ARCH3
for the SEL
OGIC Control Equation defining the trigger condition, and set Port 9 MESG2=:
\F1:A3;C/\F2:A3;C/\F3:A3;C/\F4:A3;C/\F5:A3;C/\F6:A3;C/\F7:A3;C/
for the message definition.