Fuel
Fuel type Diesel
Standard fuel tank 470 L
High autonomy fuel tank 1368 L
Lubrication
Oil capacity with filter 35 L
Min. Oil pressure 0.7 bar
Nominal oil pressure 6 bar
Oil consumption (100 % load) 0,06 L/h
Oil sump capacity 28 L
Type of lubricant Genlub
Cooling
Engine capacity with radiator 41 L
Max coolant temperature 103 °C
Fan power 17.8 kW
Ventilator air flow 7.2 m
/s
Refrigerant type Gencool
Thermostat 82-92°C
Alternator data
● Compliant with NEMA MG21 standards, UTE NF C51.111,
VDE 0530, BS 4999, IEC 34.1, CSA
● The alternator is protected against short circuits
● Vacuum impregnation, epoxy winding, IP23 protection rating
Type LEROY SOMER LSA462VL12
Number of phases 3
Power factor (cos Phi) 0.8
Number of poles 4
Excitation type AREP
Voltage regulator R450
Short-circuit current 3 IN
Number of bearings 1
Coupling Direct
Control unit(s)
TELYS
Standard specifications:
Voltmeter, Ammeter, Frequency meter
Alarms and faults
:
Oil pressure, Water temperature, Start failure, Overspeed,
Alternator min/max, Battery voltage min/max, Emergency stop
Engine parameters
:
Timer, Oil pressure, Water temperature, Fuel level, Engine
speed, Battery voltage
KERYS
Coupling
: pre-programmed coupling mode selector.
Electrical measurements
:
Voltmeter, Ammeter, Frequency meter
Alarms and faults:
Oil pressure, Water temperature, Start failure, Overspeed,
Alternator min/max, Battery voltage min/max, Emergency stop
Engine parameters
:
Timer, Oil pressure, Water temperature, Fuel level, Engine
speed, Battery voltage
Additional specifications
:Coupling Website, Troubleshooting,
Assistance and maintenance, plotting and logging, load
impact, 8 configurations available, Compliance with
international standards…