9
LEROY-SOMER
2011.01/ h
Installation and maintenance
LSA 46.2 - 4 POLES
ALTERNATORS
3856 en -
3.3.2 - Terminal connection: 6 wire (not possible with the R 250)
Connection codes Voltage L.L Factory connection
3-phase
N
T1
T4
T3
T6
T5
T2
L1(U)
L3(W)
L2(V)
D
L1(U)
L2(V)
L3(W)
L1(U)
L2(V)
L3(W)
NDE
NDE
N
T3
T2
T1
T4
T5
T6
L1(U)
L3(W)
T1
T4
T3
T6
T5
T2
L2(V)
F
T3
T2
T1
T5
T4
T6
1 phase or 3-phase
(
*
)
Winding
60 Hz50 Hz
440
380 - 416
-
-
Winding
60 Hz50 Hz
R 450 voltage detection :
0 => (T3) / 220 V => (T2)
Operating phases : L2 (V), L3 (W) single phase
380 - 415
380 - 480
6S
7S
8S
6S
7S
8S
220 - 240 220 - 277
240 - 254
-
-
220 - 240
9S -
600
R 450 voltage detection :
0 => (T3) / 380 V => (T2)
Winding 9 : R 450 voltage detection
+ transformer (See specific diagram)
In case of reconnection, ensure that the AVR voltage detection is correct !
The factory can supply a set of flexible shunts and special connection links as an option for making these connections. (*).
3.3.3 - Option connection diagram
R 791 T interference suppression kit (standard for CE marking)
Remote voltage potentiometer
Black
Black
Black
Blue
White
Connections
A D F
T1 T1 T1
T2 T2 T2
T3 T3 T3
N N
Voltage adjustment
via remote potentiometer
ST4