4
Installation notes
MOVI-C® CONTROLLER power UHX85A / power eco UHX84A
Manual – MOVI-C
®
CONTROLLER
19
Pin assignment
Use prefabricated, shielded RJ45 plug connectors compliant with IEC 11801, edi-
tion2.0, category5.
2104906251
A = View from front
B = View from back
[1] Pin 1 TX+ Transmit Plus
[2] Pin 2 TX– Transmit Minus
[3] Pin 3 RX+ Receive Plus
[4] Pin 6 RX– Receive Minus
4.1.5 EtherCAT
®
/SBus
PLUS
interface (LAN 2) connection
EtherCAT
®
/SBus
PLUS
(connection LAN 2) serves as system bus master of the fast
SBus
PLUS
.
EtherCAT
®
/SBus
PLUS
bus topology
EtherCAT
®
/SBus
PLUS
is designed for linear bus structure with RJ45 connectors. The
EtherCAT
®
/SBus
PLUS
slave units are connected to LAN 2 via a shielded twisted-pair
cable.
INFORMATION
According to IEC802.3, the maximum cable length for 10/100 MBd Ethernet (10Ba-
seT/100BaseT), e.g. between two EtherCAT
®
/SBus
PLUS
stations, is 100m.
Bus termination
Bus termination (for example with bus terminating resistors) is not necessary. The sys-
tem detects automatically if there is no subsequent device connected to a device.
Setting the station address
EtherCAT
®
/SBus
PLUS
devices from SEW‑EURODRIVE do not have an address that
can be set on the unit. The units are detected by their position in the bus structure and
are assigned an address by the EtherCAT
®
/SBus
PLUS
master.
22781455/EN – 05/2016