EasyManua.ls Logo

SEW-Eurodrive MOVI-C Series - Pin Assignment X21 and X22; Shielding and Routing Bus Cables

SEW-Eurodrive MOVI-C Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Installation notes
MOVI-C® CONTROLLER power UHX85A – R / power eco UHX84A–R
Manual – MOVI-C
®
CONTROLLER
25
4.3.2 Pin assignment X21 and X22
Use prefabricated, shielded RJ45 plug connectors compliant with IEC 11801, edi-
tion2.0, category5.
[3]
[2]
[1]
2
3
6
1
[6]
A B
6139704459
A View from front B View from back
[1] Pin 1 TX+ Transmit Plus [2] Pin 2 TX– Transmit Minus
[3] Pin 3 RX+ Receive Plus [6] Pin 6 RX– Receive Minus
4.3.3 Shielding and routing bus cables
NOTICE
Risk of a compensating current flowing as a result of incorrect bus cable type, im-
proper shielding and/or improperly routed bus cables.
Possible damage to property.
In case of fluctuations in the ground potential, a compensating current may flow
via the bilaterally connected shield that is also connected to the protective earth
(PE). Make sure you supply adequate equipotential bonding in accordance with
relevant VDE regulations in such a case.
Only use shielded cables and connection elements that meet the requirements of cat-
egory 5, class D according to IEC11801 edition 2.0.
Correct shielding of the bus cable attenuates electrical interference that can occur in
industrial environments. The following measures ensure the best possible shielding:
Manually tighten the mounting screws on the connectors, modules, and equipoten-
tial bonding conductors.
Use only connectors with a metal housing or a metalized housing.
Connect the shielding in the connector over a wide surface area.
Apply the shielding of the bus cable on both ends.
Route signal and bus cables in separate cable ducts. Do not route them parallel to
power cables (motor leads).
Use metallic, grounded cable racks in industrial environments.
Route the signal cable and the corresponding equipotential bonding close to each
other using the shortest possible route.
Avoid using plug connectors to extend bus cables.
Route the bus cables closely along existing grounding surfaces.
22781455/EN – 05/2016

Table of Contents

Related product manuals