Requirement for display:
■
more? menu: Yes option
■
Menu MFx On: Enable option
■
Functn parameter: Dist option
Table 14: MF1 – Dist submenu
Parameter Description
Limit Set switching threshold for the distance value. The digital output is activated
when the current distance value exceeds the set switching threshold.
Options
•
–300,000 … + 300,000 [mm]
Factory setting
•
1,990 [mm]
NOTE
Because the display can only handle six digits, only negative values down to
–99999 can be input via the operating buttons.
Via SOPAS ET or an existing fieldbus interface, the entire value range is
available as input. For values smaller than –99999, the highest decimal
place is truncated in the display.
inactive
active
Limit
Hyst
Dist.
Figure 22: Representation of the Dist function
Limit Distance-based switching threshold
Hyst Hysteresis of switching threshold
Dist Measured distance
Hyst Sets hysteresis for the switching threshold.
Options
•
1… +300,000 [mm]
Factory setting
•
10 [mm]
7.1.9 MF1 – Speed submenu
In this submenu, you can parameterize the MF1 as a speed switching output.
Requirement for display:
•
more? menu: Yes option
•
Menu MFx On: Enable option
•
Functn parameter: Speed option
OPERATION 7
8016994/19HB/2022-03-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro EtherNet/IP
37