PROFIBUS DP communication module
9.12 Data sets (BS)
3RW44 soft starters
196 Manual, 03/2017, NEB535219502000/RS-AB/008
341 4
1
Asymmetry tripping F24 Tripping of the motor due to
asymmetry.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
334 4
2
I
e
limit value overshot F7 Limit exceeded, alarm bit is updated
335 4
3
I
e
limit value undershot F8 Limit undershot, alarm bit is
336 4
4
I
e
current limit tripping F24 Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
5
6
339 4
7
Motor stalled - switched off F24 Trip, stalling current detected for
longer than the permitted stalling
time.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
with "trip reset".
0
States of the inputs
"1" = active, HIGH level is present
"0" = inactive, LOW level is present
Alarm bit is updated continually.
345 5
1
Input 2 -
2
3
4-7
342 6
0
Ground fault detected - Ground fault is present, alarm bit is
343 6
1
Ground fault tripping F24 Tripping of the motor due to ground
fault.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
353 6
2
Quick stop active F26, F24 Tripping of the motor due to quick
stop.
Alarm bit is automatically deleted
when the cause of the fault has
been removed and acknowledged
3