Configuring
Application Module FM 458-1 DP - User Manual 4-59
A5E01078222-02 Edition 03.2009
A detailed description of the "Automatic mode: Communications" mode to
transfer tables from an S7 control to a SIMATIC FM 458-1 DP application
module is provided in the Section "Automatic mode: Communications"
(Page 4-64).
4.7.1.3 Function block WR_TAB
The function block WR_TAB is used to transfer tables from one S7
control to a SIMATIC FM 458-1 DP application module. The tabular
values (permissible data types are REAL and double integer) are saved
in a data block. They are transferred from WR_TAB to the function blocks
TAB and TAB_D on the SIMATIC FM 458-1 DP application module,
which then internally manages the tabular values.
The WR_TAB should be configured on the control side. The tabular
values are transferred from one S7-400 control to a SIMATIC FM 458-1
DP application module via the P bus. All of the values are always
transferred, which are in the DB specified at the DBNUM input.
WR_TAB
Block activation
BO EN TABTEL W
Number of data blocks to transfer the
complete DB contents
Request to write a new table
BO REQTAB CNTTEL W
Number of data blocks already
transferred
Request to write the tabular
values in the data block
BO REQDB STATUS W
Actual processing status
Last data block for the table
BO LASTDB ERROR W
If required fault messages
Logical module address
W LADDR DONE B
Status parameter DONE: Send
operation completed
Data set number for the read
and write data set
BY RECNUM
Data block number
W DBNUM
TIMEOUT time for receiving
the acknowledge telegram from
the FM module
DW TFT
Symbol