Product description
2-42 Application Module FM 458-1 DP - User Manual
A5E01078222-02 Edition 03.2009
2.4.4 Status displays
The following LED display applies for each of the two SIMOLINK
interfaces of the EXM448-2.
LED Status Diagnostics information
green dark /
bright
No net data traffic via SIMOLINK, bus cable is either not
connected or defective.
flashing Error-free net data transfer via SIMOLINK
red dark Simolink interface power supply faulted
flashing Simolink interface in operation
yellow dark/
bright
No data transfer with the basic unit
flashing Data transfer with the basic unit is ok
Table 2-22 Status displays of the Simolink interfaces of the EXM 448-2
communications-expansion module
2.4.5 Technical data
Communications expansion module
EXM 448-2
6DD1607-0EA2
Rated voltage +5 V
Typical, current drain 0.5 A
Power loss, typ. 2.5 W
ambient temperature
max. 40 C
Assignment, slots 1
Dimensions W x H x D [mm] 25 x 290 x 210
Weight 0.85 kg
Order No.
Voltage, currents
Power loss
ambient
temperature
Dimensions