2.2.5 Incremental encoder settings
Switches S1 and S3 are used to change over between 15V and 5V
encoders. Tracks A/VW and B/RW have a common switch, track N/- of a
channel has its own switch, which can be used to set the appropriate
encoder type:
Switch open (OFF): 15 V encoder: Switching threshold = 7 V
Switch closed (ON): 5 V encoder: Switching threshold = 0 V
15 V encoders 5 V encoders
Encoder Switch Switch
Channel Track Numbr Position Numbr Position
Encoder 1 A / VW
B / RW
S1, 1 OFF S1, 1 ON
N / - S3, 1 OFF S3, 1 ON
Encoder 2 A / VW
B / RW
S1, 2 OFF S1, 2 ON
N / - S3, 2 OFF S3, 2 ON
Encoder 3 A / VW
B / RW
S1, 3 OFF S1, 3 ON
N / - S3, 3 OFF S3, 3 ON
Encoder 4 A / VW
B / RW
S1, 4 OFF S1, 4 ON
N / - S3, 4 OFF S3, 4 ON
Encoder 5 A / VW
B / RW
S1, 5 OFF S1, 5 ON
N / - S3, 5 OFF S3, 5 ON
Encoder 6 A / VW
B / RW
S1, 6 OFF S1, 6 ON
N / - S3, 6 OFF S3, 6 ON
Encoder 7 A / VW
B / RW
S1, 7 OFF S1, 7 ON
N / - S3, 7 OFF S3, 7 ON
Encoder 8 A / VW
B / RW
S1, 8 OFF S1, 8 ON
N / - S3, 8 OFF S3, 8 ON
Table 2-19 Switch settings for 5 V- and 15 V encoders
!
WARNING
When the switch is closed (on), the input voltage may not exceed the
voltage range of the 5V encoder, as otherwise the module would be
thermally overloaded.