Configuring
Application Module FM 458-1 DP - User Manual 4-61
A5E01078222-02 Edition 03.2009
The following errors can occur and are displayed at the ERROR output:
Error code Explanation Remedy
0xB210 OK -
0xB211 Logical module address invalid Specify a valid module address at input
LADDR.
0xB212 Data set number not valid Check the data set number for P bus
communications.
0xB213 Invalid table data format Tabular values must have data type REAL for
the TAB and data type DINT for the TAB_D.
0xB214 The data format of the new data set
does not match that of the previously
transferred data set
Ensure that all of the tabular values have the
same data format.
0xB215 FM 458-1 DP does not respond Check the communications connection and
configuring.
0xB216 Table is too large Transfer the table in sub-sets, i.e. either
distribute tabular values over several DBs or
after each partial transfer write new
(additional) tabular values into DB and
transfer.
0xB217 Table is not complete (X / Y values) Complete the table, there must be a Y value
for each X value.
0xB218 REQTAB is reset during processing Transfer the tabular values again.
0xB219 REQDB reset during processing Transfer the tabular values again.
0xB21A DB number is not valid Specify a valid DB number.
0xB21B TIMEOUT when receiving the
acknowledge telegram
Check the communications coupling and
configuring. Transfer the tabular values again
0xB21C Invalid processing status Check the configuring of the WR_TAB.
Errors associated with the SFC58 or SFC59 are displayed at the ERROR
output.
If an error occurred during communications with the FB TAB, then the
error messages of FB TAB and FB TAB_D are directly displayed at the
ERROR output.