Product description
Application Module FM 458-1 DP - User Manual 2-23
A5E01078222-02 Edition 03.2009
Depending on the required function (signal conversion, LED display),
different interface modules (max. 5) can be connected to the binary
inputs and outputs as well as the absolute value encoder. For this
particular case, cable SC62 must be used. This cable has five cable
ends, which can be used to connect an appropriate number of interface
modules. The following interface modules can be used:
Designation Function
SB10 Direct connection (1:1 connection)
of 8 binary I/O, LED, no signal conversion
SB61 8 Binary inputs, conversion 24V / 48V to 24V, LED, electrical
isolation
SB71 8 Binary outputs, conversion 24V to 24V / 48V (transistor),
LED, electrical isolation
SU12 10 signals can be directly connected, no signal conversion
Table 2-12 Interface modules which can be connected to X3 using SC62
Only specific signal types are available at the particular cable ends which
can be used for the matching interface modules:
Module
type
Terminal
1)
Significance
SB10
x
5x
1:1 screw terminal connection
Signal
Reference potential (Ground or P24)
SB61
x
1x
5x
Binary inputs 24/48 V
24 V binary input
48 V binary input
Reference
SB71
x
5x
Binary outputs (transistor)
Signal
Ground
1)
Screw terminals X = 1 ... 8
Table 2-13 Terminal assignment of the interface modules
Connecting X3
with cable SC62