Product description
Application Module FM 458-1 DP - User Manual 2-29
A5E01078222-02 Edition 03.2009
Number 5
Version Differential inputs
Electrical isolation No
Input voltage range - 10 V to + 10 V
Resolution 12 bit
Conversion time per channel, max approx.10 µs – 100ksps sampling
rate
Accuracy
Integral linearity error, max.
Gain error, max.
Offset error, max.
1/2 LSB
0.3 %
10 LSB
Input resistance
20 k
Input filter 34 kHz
Incorrect polarity protection No
Number 8
Electrical isolation No
External power supply
Nominal voltage
Permissible range
Briefly
Max. current drain, without load
24 V
20 V to 30 V
35 V (for max. 0.5 sec.)
20 mA
Output voltage range
For a 0 signal, max.
For a 1 signal, min.
3 V
ext. power supply voltage, – 2.5 V
Output current
For a 0 signal, min.
For a 1 signal
Nominal value
Brief, permissible range, max.
-20 µA
30 mA
100 mA
Delay time 100 µs
Switching frequency of the outputs
for ohmic load, max.
6 kHz
Short-circuit protection with respect to
Ground
External power supply
Yes
No
Short-circuit current, max. 250 mA
Total currents of the outputs 8 x 30 mA
Limiting inductive switch-off voltages ext. power supply voltage +1 V