Configuring
Application Module FM 458-1 DP - User Manual 4-25
A5E01078222-02 Edition 03.2009
Master status
Outputs information specific to the master:
Output Significance
MST Status of DP-Masters: Stop (40h), Clear (80h), Operate
(C0h)
ID Ident-No. : 80EBh for X3 on FM 458-1 DP; 8037h for SS on
EXM448 / EXM448-1
Table 4-5 Information specific to the master
Block DPSLDG: Slave diagnostics
Output of slave diagnostics data.
The SEL data entry corresponds to the slave PROFIBUS address.
The diagnostics data is dependent on the slave type.
The first 16-byte slave diagnostic data are output.
Additional slave diagnostic data can be output with SEL>1000.
Further information
on slave-specific diagnostics data, refer to the User Documentation for
the individual PROFIBUS slaves.
Connection
ST1 Status 1
ST2 Status 2
ST3 Status 3
MPA Master PROFIBUS address
ID ID No.
Diagnostics
acc. to the
Standard
6 bytes
D01 – D59 Device-specific diagnostics data (refer to the User Documentation for the
particular PROFIBUS slaves)
Table 4-6 Overview of the structure of the diagnostics data for DP slaves
Diagnostics data of
DP slaves