Configuring
4-38 Application Module FM 458-1 DP - User Manual
A5E01078222-02 Edition 03.2009
Bus cycle = system clock cycle Bus cycle = system bus cycle
t
SYNC Pause SYNC PausePause
SYNC telegram SYNC telegram
Telegrams for
data transfer
between the nodes
Telegrams for
data transfer
between the nodes
Fig. 4-14 SIMOLINK telegram data transfer
Telegram runtime: s 366.
All of the telegrams are sent immediately one after the other.
For instance, for a selected bus cycle time of 0.6 ms, the SL master
can transfer
one double word each to a max. of 91 slaves/transceiver, or
4 double words each to a max. of 22 slaves/transceiver
The remaining times are intervals where a telegram is not sent (NOP).
Master-slave process data transfer:
up to 200 slaves/transceiver can be addressed with address gaps
up to 8 double words individually for each slave/transceiver
own process data for each slave/transceiver
Dispatcher transceiver process data transfer:
up to 200 consecutively addressed transceivers
up to 8 double words
the same number of used channels for dispatcher and transceiver
(nodes with a max. number of double words defines the number
of channels for all)
Data transfer rate: 11 Mbit/s
Bus topology: Fiber-optic cable ring, each node as
signal amplifier
Max. distance between two nodes:
40 m for plastic fiber-optic cables, or
300 m for glass fiber-optic cables.