Product Description
5.4 Long Cable Filters
Product User Manual
Operating Instructions, Version AE 12/2009, A5E01454341C
99
Table 5- 26 Fifteen Cell Output Filter, Inductance
Cell Size L, Inductance L % @ 50Hz L % @ 60Hz CT Ratio (# of turns)
40 A 37.90 mH 7.50 9.00 20
70 A 22.00 mH 7.62 9.14 30
100 A 15.90 mH 7.87 9.44 50
140 A 11.00 mH 7.62 9.14 50
200 A 7.00 mH 6.93 8.31 50
260 A 5.80 mH 7..46 8.95 50
Note
Actual project L and C values are subject to change.