EasyManua.ls Logo

Siemens 6SR41 series - Figure 6-15 Inverse Time-To-Trip Curves Left - Idle State, Right - Run State

Siemens 6SR41 series
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application and Operation
6.13 Input Side Monitoring and Protection
Product User Manual
Operating Instructions, Version AE 12/2009, A5E01454341C
139
Implementation
The follwing Figure shows the implementation of the Drive Loss fault circuit.
,QSXW3RZHU
2XWSXW3RZHU ,QSXW7KUHVKROG
)DXOW
'ULYH/RVVHV
,QYHUVH7LPH


Figure 6-14 Implementation of the Drive Loss Fault Circuit
Inverse Time Curve
The follwing Figure shows the inverse time-to-trip curves as a function of Drive Losses. Each
plot shows two curves – one for Idle State and the other for Run State (slightly longer time to
trip). For software versions 2.22 and lower, a fixed trip time of one second was used instead
of the curves shown next.
   
   








'ULYH/RVVHV
7LPHWRWULSV
7LPHWRWULSV
'ULYH/RVVHV
5XQ6WDWH
,GOH6WDWH
5XQ6WDWH
,GOH6WDWH
([FHVVLYH'ULYH/RVV3URWHFWLRQ,GOH
([FHVVLYH'ULYH/RVV3URWHFWLRQ5XQQLQJ
Figure 6-15 Inverse Time-To-Trip Curves Left - Idle State, Right - Run State

Table of Contents

Related product manuals