Signal Type Signal Name Function
Digital Input IDI-2B Output Reactor Winding Temperature, High (Else SPARE)
Digital Input IDI-3B Output Reactor Winding Temperature, High-High (Else SPARE)
Digital Input IDI-0C Cabinet Door Interlock (Else SPARE)
Digital Input IDI-1C SPARE
Digital Input IDI-2C SPARE
Digital Input IDI-3C Transformer Air Flow Temperature, High
Digital Input IDI-0D Transformer Air Flow Temperature, High-High
Digital Input IDI-1D Cooling Blower TBLW1 O.K.
Digital Input IDI-2D Cooling Blower CBLW2 O.K.
Digital Input IDI-3D Redundant Cooling Blower TBLW2 O.K. (Optional)
Digital Input IDI-0E Redundant Cooling Blower CBLW2 O.K. (Optional)
Digital Input IDI-1E SPARE
Digital Input IDI-2E SPARE
Digital Input IDI-3E Latch Fault Relay (LFR) Feedback
Digital Output IDO-0 Speed Demand in Local at VFD
Digital Output IDO-1 Drive Ready to Run
Digital Output IDO-2 Drive Running
Digital Output IDO-3 Drive Alarm
Digital Output IDO-4 Drive Fault
Digital Output IDO-5 ProToPS, Process Alarm (Else SPARE)
Digital Output IDO-6 ProToPS, Process Trip Alarm (Else SPARE)
Digital Output IDO-7 SPARE
Digital Output IDO-8 Cooling Blower TBLW1 Starter
Digital Output IDO-9 Cooling Blower TBLW2 Starter (Optional)
Digital Output IDO-10 Cooling Blower CBLW1 Starter
Digital Output IDO-11 Redundant Cooling Blower 2 CBLW2 Starter (Optional)
Digital Output IDO-12 SPARE
Digital Output IDO-13 SPARE
Digital Output IDO-14 Coordinated Input Protection Scheme
Digital Output IDO-15 Latch Fault Relay (LFR), Set Pulse
Analog Input IAI-1 Remote Speed Demand, 4-20 mADC
Analog Input IAI-2 SPARE
Analog Input IAI-3 SPARE
Analog Output IAO-1 Motor Speed, 4-20 mADC
Analog Output IAO-2 Motor Torque, 4-20 mADC
Table 5- 16 Twenty-Four Cell, GenIV, Core Hardwired I/O Assignments
(Subject to Change. Always refer to the project "A" and "B" for I/O assignments)
Signal Type Signal Name Function
Digital Input IDI-0A Remote Inhibit
Digital Input IDI-1A Remote Start

Table of Contents