Product Description   
5.3 Cabinet Details 
  Product User Manual  
64  Operating Instructions, Version AE 12/2009, A5E01454341C 
The input and output medium voltage terminals (L1, L2, L3 and T1, T2, T3) are offset from 
one another and have two NEMA one-hole pattern configurations (vertical and horizontal) to 
facilitate top or bottom cable termination (see Figure " Medium Voltage Terminations (L1, L2, 
L33, or T1, T2, T3"). 
 
 
Note 
The GenIV design is best accommodated for single conductor single core medium voltage 
cables. Three conductor single core cables must be broken into their individual conductors 
prior to entering the gland plate of the VFD unit. 
 
 
Figure 5-5  Medium Voltage Terminations (L1, L2, L3, or T1, T2, T3) 
The input current transformers, output Hall Effect current transducers, and input/output 
voltage attenuators are pre-engineered according to each project's requirements. The 
metallic chassis, housing the hall effect current transducers and low voltage portion of the 
medium voltage attenuating resistors, are grounded at point GND3. The secondary of CT1 
and CT2 are also grounded to point GND3. The bypass power supply and bypass control 
circuit are used when Mechanical Cell Bypass is selected as an option. The auxiliary voltage 
transformer steps customer-supplied three phase low voltage down to single phase 120 V for 
use with the NXG II controller. This 500 VA transformer is protected by three control fuses 
(2 primary, 1 secondary) that are located in the Control Wire Way section.