7SR18 Performance Specification
Unrestricted Page 14 of 44 ©2018 Siemens Protection Devices Limited
1.6.1.7 IP Ratings
IEC60529
Type Level
Installed with cover on
Rear IP 10
Front IP 51
Installed with cover removed
Rear IP 10
Front IP 20
1.6.2 Emissions
1.6.2.1 Radiated Emissions – Enclosure Port
IEC 60255-26
Type Limits at 10 m, Quasi-peak
30 MHz to 230 MHz
40 dB(µV/m)
230 MHz to 1000 MHz
47 dB(µV/m)
1.6.2.2 Conducted Emissions – Auxiliary Supply Port
IEC 60255-26
Type
Limits
Quasi-peak Average
0.15 MHz to 0.5 MHz
79 dB(µV) 66 dB(µV)
0.5 MHz to 30 MHz
73 dB(µV) 60 dB(µV)