EasyManua.ls Logo

Siemens 7SR18 Solkor - Broken Conductor (46 BC); Figure 5.4-1 Logic Diagram: Broken Conductor Function (46 BC)

Siemens 7SR18 Solkor
417 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR18 Description Of Operation
Unrestricted ©2018 Siemens Protection Devices Limited Page 67 of 78
5.4 Broken Conductor (46BC)
The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above 46BC
Setting an output is given after the 46BC Delay.
The Broken Conductor function can be inhibited from
Inhibit 46BC A binary or virtual input.
46BC U/C Guard A minimum load current.
46BC U/C Guard Setting (0.05, 0.1... 5x In)
Figure 5.4-1 Logic Diagram: Broken Conductor Function (46BC)