7SR18 Commissioning & Maintenance Guide
Unrestricted Page 48 of 54 ©2018 Siemens Protection Devices Limited
46BC Setting 1P unbalance current
(% of 3P current)
20% 75%
25% 100%
30% 129%
35% 161%
40% 200%
46BC Setting 3P balanced current (A) 1P unbalance current (A) Measured Unbalance
current
Apply 1 A 1P unbalance current without 3P balanced current. Measure 46BC operating time.
46BC Delay setting Measured
4.3.1 ELEMENT BLOCKING
The Broken Conductor element can be blocked by Binary Input Inhibit. This functionality should be checked.
Element BI Inhibits
46BC