EasyManua.ls Logo

Siemens 7SR18 Solkor - Negative Phase Sequence Over-Current (46 NPS)

Siemens 7SR18 Solkor
417 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR18 Applications Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 17 of
63
Figure 2.3-2 Blocking Scheme Using Instantaneous Over-current Elements
Typically a time delay as low as 50 ms on the incomer 50-1 element will ensure that the incomer is not tripped for
outgoing circuit faults. However, to include for both equipment tolerances and a safety margin a minimum time
delay of 100 ms is recommended.
This type of scheme is very cost effective and provides a compromise between back-up over-current busbar
protection and dedicated schemes of busbar protection.
2.4 Negative Phase Sequence Over-current (46NPS)
The presence of Negative Phase Sequence (NPS) current indicates an unbalance in the phase currents, either
due to a fault or unbalanced load.
NPS current presents a major problem for 3-phase rotating plant. It produces a reaction magnetic field which
rotates in the opposite direction, and at twice the frequency, to the main field created by the DC excitation system.
This induces double-frequency currents into the rotor which cause very large eddy currents in the rotor body. The
resulting heating of the rotor can be severe and is proportional to (I
2
)
2
t.
Generators and Motors are designed, manufactured and tested to be capable of withstanding unbalanced current
for specified limits. Their withstand capability is specified in two parts; continuous capability based on a figure of
I
2
, and short time capability based on a constant, K, where K = (I
2
)
2
t. NPS over-current protection is therefore
configured to match these two plant characteristics.

Table of Contents

Related product manuals