7SR18 Performance Specification
Unrestricted Page 40 of 44 ©2018 Siemens Protection Devices Limited
3.2 50BF Circuit Breaker Fail
3.2.1 Reference
Parameter Value
Is Setting 0.050, 0.055… 2.0 xIn
I4 Setting 0.050, 0.055… 2.0 xIn
t
CBF1
Stage 1 Delay setting 20, 25… 60000 ms
t
CBF2
Stage 2 Delay setting 20, 25… 60000 ms
3.2.2 Operate and Reset Level
Attribute Value
I
op
Operate level
100 % Is, ± 5 % or ± 1 % In
I
reset
Reset level
<100 % I
op
, ± 5 % or ± 1 % In
Repeatability
± 1 %
Variation
-10 °C to +55 °C
≤ 5 %
f
nom
± 5 %
≤ 5 %
3.2.3 Operate and Reset Time
Attribute Value
t
op
Stage 1
t
CBF1
, ± 1 % or ± 20 ms
Stage 2
t
CBF2
, ± 1 % or ± 20 ms
Repeatability
± 1 % or ± 20 ms
Overshoot < 2 x 20 ms
Disengaging time < 20 ms