EasyManua.ls Logo

Siemens 7SR18 Solkor - Time Delayed Measured Earth Fault; Reference; Operate and Reset Level

Siemens 7SR18 Solkor
417 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR18 Performance Specification
Unrestricted Page 32 of 44 ©2018 Siemens Protection Devices Limited
2.8 51G Time Delayed Measured Earth Fault
2.8.1 Reference
Parameter Value
Is Setting 0.05, 0.06… 2.5 xIn
Char Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Tm Time Multiplier setting 1.0 (0.025,0.05…100)
t
d
Delay setting (DTL) 0, 0.01… 20 s
t
res
Reset setting ANSI DECAYING, 0, 1… 60 s
I
Applied current (for
operate time)
IDMTL 2 to 20 xIs
DTL 5 xIs
2.8.2 Operate and Reset Level
Attribute Value
I
op
Operate level
105 % Is, ± 4 % or ± 1% In
Reset level
95 % I
op
Repeatability
± 1 %
Variation
-10 °C to +55 °C
5 %
f
nom
± 5 %
5 %

Table of Contents

Related product manuals